GATE EE 2015 Set 2 — Question 52
Go beyond PYQs with Success TrackerAI-powered personalised practice and doubt support. Unlimited practice on eligible plans; AI usage limits apply.MCQ+2 / -0.67MediumDuty Ratio & EfficiencyDC-DC ConvertersPower Electronics
Power Electronics → DC-DC Converters → Duty Ratio & Efficiency
Last updated
Question
A 3-phase transformer rated for 33 kV/11 kV is connected in delta/star as shown in figure. The current transformers (CTs) on low and high voltage sides have a ratio of 500/5. Find the currents and , if the fault current is 300 A as shown in figure.

Correct answer
(A) i₁ = 1/√(3) A, i₂ = 0 A
Solution
Reading the figure
Each side has one CT, on line ; the other two lines only cross the CT pilot wires. The HV CT secondary drives and the LV CT secondary drives . The fault (300 A to ground) is on LV line .Delta connections on the HV side
The top winding runs from to , the middle from to , and the bottom winding from back round to . The bottom HV winding is on the same limb as the bottom LV (star) winding, which is the faulted phase .Turns ratio per phase
Each HV (delta) winding has 33 kV across it; each LV (star) winding has kV:LV side
The 300 A fault current flows only in LV winding and line (star neutral grounded). LV line carries no current.HV side
The bottom (–) delta winding carriesThe other two HV windings carry no current, so this winding current flows in lines and ; line carries A.CT secondary currents (ratio )
Each side has one CT, on line ; the other two lines only cross the CT pilot wires. The HV CT secondary drives and the LV CT secondary drives . The fault (300 A to ground) is on LV line .Delta connections on the HV side
The top winding runs from to , the middle from to , and the bottom winding from back round to . The bottom HV winding is on the same limb as the bottom LV (star) winding, which is the faulted phase .Turns ratio per phase
Each HV (delta) winding has 33 kV across it; each LV (star) winding has kV:LV side
The 300 A fault current flows only in LV winding and line (star neutral grounded). LV line carries no current.HV side
The bottom (–) delta winding carriesThe other two HV windings carry no current, so this winding current flows in lines and ; line carries A.CT secondary currents (ratio )
- A
- A, since LV line carries no current.
Continue learning with Success Tracker
A step still unclear? Work through it with support
Use Success Tracker to ask about the reasoning, then try another GATE EE question to check your understanding.
AI-powered practice· Unlimited practice on eligible plans
- PYQs with solutions
- Attempt available previous-year questions, then compare your reasoning with the worked solution. Coverage varies by stream.
- Practice that adapts
- Choose a topic, work on weaker areas and bookmark questions to revisit. Your attempts feed your progress tracking.
- AI doubt support
- Ask follow-up questions about a step or concept while practising, instead of stopping at the final answer.
Unlimited practice is available on eligible plans. Free practice and AI usage have limits; check the current plan allowances before choosing.
This page stays readable without an account. AI responses can be wrong; check them against the solution and source material.
More questions on DC-DC Converters
2026 Set 1 Q27The figure shows a straight-line approximation for the forward characteristics of a power diode. A…2026 Set 1 Q28Consider the circuit shown in Figure (a). A gate pulse is applied between time instants …2026 Set 1 Q34Consider the circuit shown. Assume that the diode is ideal. The supply voltage…2026 Set 1 Q47Consider the single-phase voltage source inverter circuit feeding an inductive load (). Assume…2026 Set 1 Q48Consider the boost converter circuit shown. Assume that the semiconductor devices are ideal. In…