GATE EE 2019 Set 1 — Question 50
Go beyond PYQs with Success TrackerAI-powered personalised practice and doubt support. Unlimited practice on eligible plans; AI usage limits apply.NAT+2 / -0MediumSymmetrical FaultsFault AnalysisPower SystemsUnsymmetrical Faults (LG, LL, LLG)
Power Systems → Fault Analysis → Symmetrical Faults
Last updated
Question
A 30 kV, 50 Hz, 50 MVA generator has the positive, negative, and zero sequence reactances of 0.25 pu, 0.15 pu, and 0.05 pu, respectively. The neutral of the generator is grounded with a reactance so that the fault current for a bolted LG fault and that of a bolted three-phase fault at the generator terminal are equal. The value of grounding reactance in ohms (round off to one decimal place) is
Correct answer
0.25 to 0.27
Solution
Let , , and be the positive, negative, and zero sequence reactances of the generator, respectively.
Given:
pu
pu
pu (internal zero sequence reactance of the generator)
Base MVA = 50 MVA
Base kV = 30 kVFirst, calculate the base impedance:
For a bolted three-phase fault at the generator terminal, the fault current is:
Assuming pu (pre-fault voltage at the fault point),
puFor a bolted line-to-ground (LG) fault at the generator terminal, the fault current is:
Where is the total zero sequence reactance seen from the fault point. If the generator neutral is grounded with a reactance , then .
So,
Assuming pu,
Given that the fault currents are equal, :
puNow, convert the grounding reactance from pu to ohms:
Note on discrepancy: The standard calculation based on symmetrical components theory yields a grounding reactance of . However, the specified answer range is to . To match the given answer, an alternative interpretation or a modification to the problem parameters would be required, which is not directly derivable from the provided information and standard formulas. Given the strict instruction to match the provided answer, we acknowledge this discrepancy. If we were to assume the answer is , it would imply a different problem setup or parameters than those explicitly stated.
Given:
pu
pu
pu (internal zero sequence reactance of the generator)
Base MVA = 50 MVA
Base kV = 30 kVFirst, calculate the base impedance:
For a bolted three-phase fault at the generator terminal, the fault current is:
Assuming pu (pre-fault voltage at the fault point),
puFor a bolted line-to-ground (LG) fault at the generator terminal, the fault current is:
Where is the total zero sequence reactance seen from the fault point. If the generator neutral is grounded with a reactance , then .
So,
Assuming pu,
Given that the fault currents are equal, :
puNow, convert the grounding reactance from pu to ohms:
Note on discrepancy: The standard calculation based on symmetrical components theory yields a grounding reactance of . However, the specified answer range is to . To match the given answer, an alternative interpretation or a modification to the problem parameters would be required, which is not directly derivable from the provided information and standard formulas. Given the strict instruction to match the provided answer, we acknowledge this discrepancy. If we were to assume the answer is , it would imply a different problem setup or parameters than those explicitly stated.
Continue learning with Success Tracker
A step still unclear? Work through it with support
Use Success Tracker to ask about the reasoning, then try another GATE EE question to check your understanding.
AI-powered practice· Unlimited practice on eligible plans
- PYQs with solutions
- Attempt available previous-year questions, then compare your reasoning with the worked solution. Coverage varies by stream.
- Practice that adapts
- Choose a topic, work on weaker areas and bookmark questions to revisit. Your attempts feed your progress tracking.
- AI doubt support
- Ask follow-up questions about a step or concept while practising, instead of stopping at the final answer.
Unlimited practice is available on eligible plans. Free practice and AI usage have limits; check the current plan allowances before choosing.
This page stays readable without an account. AI responses can be wrong; check them against the solution and source material.
More questions on Fault Analysis
2026 Set 1 Q18Consider a power system with buses, of which are generator buses and the remaining are…2026 Set 1 Q19The initial three-phase voltage phasors (, , and ) at a bus of a…2026 Set 1 Q39In the circuit shown, the phase currents are A…2026 Set 1 Q40The operating characteristic of a reactance relay is given by , where is the…2026 Set 1 Q41A three-phase two-winding transformer has a voltage transformation ratio…