GATE EE 2023 Set 1 — Question 20
Go beyond PYQs with Success TrackerAI-powered personalised practice and doubt support. Unlimited practice on eligible plans; AI usage limits apply.MCQ+1 / -0.33HardOvercurrent ProtectionPower System ProtectionPower SystemsDifferential & Directional
Power Systems → Power System Protection → Differential & Directional
Last updated
Question
For the three-bus power system shown in the figure, the trip signals to the circuit breakers to are provided by overcurrent relays to , respectively, some of which have directional properties also. The necessary condition for the system to be protected for short circuit fault at any part of the system between bus 1 and the R-L loads with isolation of minimum portion of the network using minimum number of directional relays is

Correct answer
(A) R₃ and R₄ are directional overcurrent relays blocking faults towards bus 2
Solution
In a power system with parallel feeders (Line 1 and Line 2), directional overcurrent relays are required at the receiving end (load end) to ensure selectivity.
1.Parallel Feeders: For a fault on Line 1, fault current flows from the source at Bus 1 through . Additionally, current flows through the healthy Line 2 to Bus 2 and then back through to the fault.
2.Selectivity: To isolate only the faulted Line 1, relay must trip, while must remain stable. If and were non-directional, both might trip for a fault on either line.
3.Directional Placement: By making and directional such that they trip only for faults in the direction of the lines (away from Bus 2) and block for faults towards Bus 2, we ensure that for a fault on Line 1, sees a forward fault and trips, while sees a reverse fault (towards the bus) and blocks.
4.Radial Feeders: Line 3 is a radial feeder. Non-directional relays at and are sufficient for its protection when coordinated with time-grading.
Therefore, the minimum requirement for directional relays is that and are directional, blocking faults towards Bus 2.Continue learning with Success Tracker
A step still unclear? Work through it with support
Use Success Tracker to ask about the reasoning, then try another GATE EE question to check your understanding.
AI-powered practice· Unlimited practice on eligible plans
- PYQs with solutions
- Attempt available previous-year questions, then compare your reasoning with the worked solution. Coverage varies by stream.
- Practice that adapts
- Choose a topic, work on weaker areas and bookmark questions to revisit. Your attempts feed your progress tracking.
- AI doubt support
- Ask follow-up questions about a step or concept while practising, instead of stopping at the final answer.
Unlimited practice is available on eligible plans. Free practice and AI usage have limits; check the current plan allowances before choosing.
This page stays readable without an account. AI responses can be wrong; check them against the solution and source material.
More questions on Power System Protection
2026 Set 1 Q18Consider a power system with buses, of which are generator buses and the remaining are…2026 Set 1 Q19The initial three-phase voltage phasors (, , and ) at a bus of a…2026 Set 1 Q39In the circuit shown, the phase currents are A…2026 Set 1 Q40The operating characteristic of a reactance relay is given by , where is the…2026 Set 1 Q41A three-phase two-winding transformer has a voltage transformation ratio…