Question
A single-phase 100 kVA, 1000 V / 100 V, 50 Hz transformer has a voltage drop of 5% across its series impedance at full load. Of this, 3% is due to resistance. The percentage regulation of the transformer at full load with 0.8 lagging power factor is
Correct answer
(A) 4.8
Solution
Given:
Voltage drop across series impedance,
Voltage drop across resistance,
We know that
(or 4%)
Power factor lagging
Percentage regulation for lagging power factor is given by:
Thus, the correct option is (A).
Voltage drop across series impedance,
Voltage drop across resistance,
We know that
(or 4%)
Power factor lagging
Percentage regulation for lagging power factor is given by:
Thus, the correct option is (A).
Continue learning with Success Tracker
A step still unclear? Work through it with support
Use Success Tracker to ask about the reasoning, then try another GATE EE question to check your understanding.
AI-powered practice· Unlimited practice on eligible plans
- PYQs with solutions
- Attempt available previous-year questions, then compare your reasoning with the worked solution. Coverage varies by stream.
- Practice that adapts
- Choose a topic, work on weaker areas and bookmark questions to revisit. Your attempts feed your progress tracking.
- AI doubt support
- Ask follow-up questions about a step or concept while practising, instead of stopping at the final answer.
Unlimited practice is available on eligible plans. Free practice and AI usage have limits; check the current plan allowances before choosing.
This page stays readable without an account. AI responses can be wrong; check them against the solution and source material.
More questions on Single-Phase Transformers
2026 Set 1 Q17A 15 kVA, 1100 V/220 V, single-phase two-winding transformer is configured as a 1.32 kV/1.1 kV…2026 Set 1 Q20A certain application requires power at a frequency of , while the available grid…2026 Set 1 Q21Which one of the following options is correct regarding the typical double-squirrel-cage structure…2026 Set 1 Q22The figure shows the single-line diagram of a synchronous generator delivering …2026 Set 1 Q31A 220V/12V single-phase transformer is designed for use in India and rated 100 VA at 50 Hz. Later,…