GATE EE 2020 Set 1 — Question 53
Go beyond PYQs with Success TrackerAI-powered personalised practice and doubt support. Unlimited practice on eligible plans; AI usage limits apply.MCQ+2 / -0.67MediumSynchronous Reactance & RegulationSynchronous MachinesElectrical Machines
Electrical Machines → Synchronous Machines → Synchronous Reactance & Regulation
Last updated
Question
The figure below shows the per-phase Open Circuit Characteristics (measured in V) and Short Circuit Characteristics (measured in A) of a 14 kVA, 400 V, 50 Hz, 4-pole, 3-phase, delta connected alternator, driven at 1500 rpm. The field current, is measured in A. Readings taken are marked as respective coordinates in the figure. Ratio of the unsaturated and saturated synchronous impedances of the alternator is closest to:

Correct answer
(A) 2.100
Solution
1.Identify Synchronous Impedance Definitions:
- Unsaturated synchronous impedance () is calculated from the air-gap line (linear portion of the OCC).
- Saturated synchronous impedance () is calculated at the rated voltage using the actual OCC curve.
- From the SCC, the characteristic is a straight line passing through and . Thus, .
- From the linear part of the OCC (air-gap line), it passes through . Thus, V_{oc(linear)} = rac{210}{2} I_f = 105 I_f.
- .
- The alternator is delta-connected, so the phase voltage equals the line voltage V.
- From the OCC curve, V occurs at A (point ).
- At A, the short-circuit current is A.
- .
- Ratio .
Continue learning with Success Tracker
A step still unclear? Work through it with support
Use Success Tracker to ask about the reasoning, then try another GATE EE question to check your understanding.
AI-powered practice· Unlimited practice on eligible plans
- PYQs with solutions
- Attempt available previous-year questions, then compare your reasoning with the worked solution. Coverage varies by stream.
- Practice that adapts
- Choose a topic, work on weaker areas and bookmark questions to revisit. Your attempts feed your progress tracking.
- AI doubt support
- Ask follow-up questions about a step or concept while practising, instead of stopping at the final answer.
Unlimited practice is available on eligible plans. Free practice and AI usage have limits; check the current plan allowances before choosing.
This page stays readable without an account. AI responses can be wrong; check them against the solution and source material.
More questions on Synchronous Machines
2026 Set 1 Q17A 15 kVA, 1100 V/220 V, single-phase two-winding transformer is configured as a 1.32 kV/1.1 kV…2026 Set 1 Q20A certain application requires power at a frequency of , while the available grid…2026 Set 1 Q21Which one of the following options is correct regarding the typical double-squirrel-cage structure…2026 Set 1 Q22The figure shows the single-line diagram of a synchronous generator delivering …2026 Set 1 Q31A 220V/12V single-phase transformer is designed for use in India and rated 100 VA at 50 Hz. Later,…