Question
A 25 kVA, 400 V, -connected, 3-phase, cylindrical rotor synchronous generator requires a field current of 5 A to maintain the rated armature current under short-circuit condition. For the same field current, the open-circuit voltage is 360 V. Neglecting the armature resistance and magnetic saturation, its voltage regulation (in % with respect to terminal voltage), when the generator delivers the rated load at 0.8 pf leading, at rated terminal voltage is ___________.
Answer checking is unavailable for this question. You can review the published solution without a score.
Solution
1.Calculate rated phase current ():
Since the generator is -connected, the phase voltage is equal to the line voltage V.Rated phase current A.
2.Calculate synchronous reactance ():
From the short-circuit test, A at A.From the open-circuit test, V at A. Since it is -connected, V.
.
3.Calculate excitation voltage () for 0.8 pf leading:
For leading power factor, the phasor equation is . In magnitude form:Given , so .
V.
4.Calculate voltage regulation:
Voltage Regulation .Continue learning with Success Tracker
A step still unclear? Work through it with support
Use Success Tracker to ask about the reasoning, then try another GATE EE question to check your understanding.
AI-powered practice· Unlimited practice on eligible plans
- PYQs with solutions
- Attempt available previous-year questions, then compare your reasoning with the worked solution. Coverage varies by stream.
- Practice that adapts
- Choose a topic, work on weaker areas and bookmark questions to revisit. Your attempts feed your progress tracking.
- AI doubt support
- Ask follow-up questions about a step or concept while practising, instead of stopping at the final answer.
Unlimited practice is available on eligible plans. Free practice and AI usage have limits; check the current plan allowances before choosing.
This page stays readable without an account. AI responses can be wrong; check them against the solution and source material.
More questions on Synchronous Machines
2026 Set 1 Q17A 15 kVA, 1100 V/220 V, single-phase two-winding transformer is configured as a 1.32 kV/1.1 kV…2026 Set 1 Q20A certain application requires power at a frequency of , while the available grid…2026 Set 1 Q21Which one of the following options is correct regarding the typical double-squirrel-cage structure…2026 Set 1 Q22The figure shows the single-line diagram of a synchronous generator delivering …2026 Set 1 Q31A 220V/12V single-phase transformer is designed for use in India and rated 100 VA at 50 Hz. Later,…