GATE EE 2025 Set 1 — Question 43
Go beyond PYQs with Success TrackerAI-powered personalised practice and doubt support. Unlimited practice on eligible plans; AI usage limits apply.MCQ+2 / -0.67HardConnections & Vector GroupsThree-Phase TransformersElectrical Machines
Electrical Machines → Three-Phase Transformers → Connections & Vector Groups
Last updated
Question
The transformer connection given in the figure is part of a balanced 3-phase circuit where the phase sequence is “abc”. The primary to secondary turns ratio is 2:1. If , then the relationship between and will be

Correct answer
(A) I_A I_(ad) = 12√(3) and I_(ad) lags I_A by 30^.
Solution
Connection. The primary is star connected, so the primary line current is also the primary winding current of that limb. The secondary is delta connected, so , , are the secondary winding (phase) currents and , , are the secondary line currents.Step 1 - ampere-turn balance on one limb. With ,and is in phase with .Step 2 - delta line current. At the secondary terminal , KCL givesFor the sequence take , then and (consistent with ). HenceSo the secondary line current is times the winding current and lags it by .Step 3 - combine.Thereforeand, since is in phase with , lags by .Options (C) and (D) invert the magnitude ratio, and option (B) has the wrong sign of the phase shift.Answer: (A)
Continue learning with Success Tracker
A step still unclear? Work through it with support
Use Success Tracker to ask about the reasoning, then try another GATE EE question to check your understanding.
AI-powered practice· Unlimited practice on eligible plans
- PYQs with solutions
- Attempt available previous-year questions, then compare your reasoning with the worked solution. Coverage varies by stream.
- Practice that adapts
- Choose a topic, work on weaker areas and bookmark questions to revisit. Your attempts feed your progress tracking.
- AI doubt support
- Ask follow-up questions about a step or concept while practising, instead of stopping at the final answer.
Unlimited practice is available on eligible plans. Free practice and AI usage have limits; check the current plan allowances before choosing.
This page stays readable without an account. AI responses can be wrong; check them against the solution and source material.
More questions on Three-Phase Transformers
2026 Set 1 Q17A 15 kVA, 1100 V/220 V, single-phase two-winding transformer is configured as a 1.32 kV/1.1 kV…2026 Set 1 Q20A certain application requires power at a frequency of , while the available grid…2026 Set 1 Q21Which one of the following options is correct regarding the typical double-squirrel-cage structure…2026 Set 1 Q22The figure shows the single-line diagram of a synchronous generator delivering …2026 Set 1 Q31A 220V/12V single-phase transformer is designed for use in India and rated 100 VA at 50 Hz. Later,…